標(biāo)準(zhǔn)號(hào):IEC 60898-1-2002
中文標(biāo)準(zhǔn)名稱:電氣附件.家用和類似設(shè)施用的過電流保護(hù)斷路器.第1部分:交流操作斷路器
英文標(biāo)準(zhǔn)名稱:Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installations - Part 1: Circuit-breakers for a.c. operation
標(biāo)準(zhǔn)類型:K31
發(fā)布日期:1999/12/31 12:00:00
實(shí)施日期:1999/12/31 12:00:00
中國標(biāo)準(zhǔn)分類號(hào):K31
國際標(biāo)準(zhǔn)分類號(hào):29.120.50
適用范圍:This part of IEC 60898 applies, to a.c. air-break circuit-breakers for operation at 50 Hz or 60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not exceeding 125 A and a rated short-circuit capacity not exceeding 25 000 A.
As far as possible, it is in line with the requirements contained in IEC 60947-2.
These circuit-breakers are intended for the protection against overcurrents of wiring installations of buildings and similar applications; they are designed for use by uninstructed people and for not being maintained.
They are intended for use in an environment with pollution degree 2.
They are suitable for isolation.
Circuit-breakers of this standard, with exception of those rated 120 V or 120/240 V (see table 1), are suitable for use in IT systems provided that the requirements of IEC 60364-4-473:1977 + A1:1998 are complied with.
This standard also applies to circuit-breakers having more than one rated current, provided that the means for changing from one discrete rating to another is not accessible in normal service and that the rating cannot be changed without the use of a tool.
This standard does not apply to
- circuit-breakers intended to protect motors;
- circuit-breakers, the current setting of which is adjustable by means accessible to the user.
For circuit-breakers having a degree of protection higher than IP20 according to IEC 60529, for use in locations where arduous environmental conditions prevail (e.g. excessive humidity, heat or cold or deposition of dust) and in hazardous locations (e.g. where explosions are liable to occur), special constructions may be required.
Requirements for circuit-breakers for a.c. and d.c. operation are given in IEC 60898-2.
Requirements for circuit-breakers which incorporate residual current tripping devices are to be found in IEC 61009-1, IEC 61009-2-1, and IEC 61009-2-2.
A guide for co-ordination under short-circuit conditions between a circuit-breaker and another short-circuit protective device (SCPDs) is given in annex D.
NOTE 1 For more severe overvoltage conditions, circuit-breakers complying with other standards (e.g. IEC 60947-2) should be used.
NOTE 2 For an environment with a higher pollution degree, enclosures giving the appropriate degree of protection should be used.
NOTE 3 Circuit-breakers within the scope of this standard may also be used for protection against electric shock in case of fault, depending on their tripping characteristics and on the characteristics of the installation. The criterion of application for such purposes is dealt with by installation rules.
This standard contains all requirements necessary to ensure compliance with the operational characteristics required for these devices by type tests.
It also contains the details relative to test requirements and methods of testing necessary to ensure reproducibility of test results.
This standard states
a) the characteristics of circuit-breakers;
b) the conditions with which circuit-breakers shall comply, with reference to:
1) their operation and behaviour in normal service;
2) their operation and behaviour in case of overload;
3) their operation and behaviour in case of short-circuits up to their rated short-circuit
capacity;
4) their dielectric properties;
c) the tests intended for confirming that these conditions have been met and the methods to be adopted for the tests;
d) the data to be marked on the devices;
e) the test sequences to be carried out and the number of samples to be submitted for certification purposes (see annex C);
f) the co-ordination under short-circuit conditions with another short-circuit protective device (SCPD) associated in the same circuit (see annex D);
g) the routine tests to be carried out on each circuit-breaker to reveal unacceptable variations in material or manufacture, likely to affect safety (see annex I).
相關(guān)標(biāo)準(zhǔn)
百檢網(wǎng)專注于為第三方檢測機(jī)構(gòu)以及中小微企業(yè)搭建互聯(lián)網(wǎng)+檢測電商服務(wù)平臺(tái),是一個(gè)創(chuàng)新模式的檢驗(yàn)檢測服務(wù)網(wǎng)站。百檢網(wǎng)致力于為企業(yè)提供便捷、高效的檢測服務(wù),簡化檢測流程,提升檢測服務(wù)效率,利用互聯(lián)網(wǎng)+檢測電商,為客戶提供多樣化選擇,從根本上降低檢測成本提升時(shí)間效率,打破行業(yè)壁壘,打造出行業(yè)創(chuàng)新的檢測平臺(tái)。
百檢能給您帶來哪些改變?
1、檢測行業(yè)全覆蓋,滿足不同的檢測;
2、實(shí)驗(yàn)室全覆蓋,就近分配本地化檢測;
3、工程師一對一服務(wù),讓檢測更精準(zhǔn);
4、免費(fèi)初檢,初檢不收取檢測費(fèi)用;
5、自助下單 快遞免費(fèi)上門取樣;
6、周期短,費(fèi)用低,服務(wù)周到;
7、擁有CMA、CNAS、CAL等權(quán)威資質(zhì);
8、檢測報(bào)告權(quán)威有效、中國通用;